Re: Kohler 6.5KW CZ generator blowing fuse

by john jacob <j.jacob-bikehead@[EMAIL PROTECTED] > Jan 29, 2008 at 02:09 PM

GSS wrote:
> I have a gas powered 6.5 KW Kohler generator Model 6.5CZ that blows
> the 10 amp input fuse whenever I shut it down from the engine mounted
> or remote kill switches. 

This may not be related. However, I have a 20kw Kohler that kept blowing 
fuses for no reason. I found out the improper fuse was installed. A 10 
amp high heat ceramic fuse should have been used. The heat given off 
from the generator engine would heat up the fuse, and de-rate it. A 
ceramic fuse is designed to operate in high ambient temperatures.

I hope this helps.
John
 